SZ-DOC-W5-1.pdf LTU/NTU
Version: 1.5 Operating Manual
37 Revision: 2002-09-10
Receiving AIS at the V3 reference point (AIS-V3)
nx64 kbit/s Interface:
Loss of codirectional clock or clock rate mismatch (clock mode: nx64 Port) on the nx64
kbit/s side (LOC),
Data Terminal Ready (DTR, circuit 108/2) on the nx64 Port is detected as 'OFF'. For X.21, the
control-signal (C) is represented by DTR.
The loops 1 and 2 can be controlled by the circuits 140 (RL) and 141 (LL), thus the alarms
LOOP1 and LOOP2 can also be caused by the nx64 kbit/s interface
Displaying an urgent alarm has a higher priority than displaying a non-urgent one, i.e. an amber
alarm will be “overwritten” by a red alarm.
5.1.2.2 Remote LED
The remote LED is an image of the local LED of the remote slave station (see previous LED-table
for exceptions). When configured as “slave” no remote access is possible, so the remote LED is
turned off.
5.2 Alarm Relays
5.2.1 LTU
There are two concepts for signaling the alarm status of the LTU in the subrack.
Each LTU has an open collector alarm output working on a common signaling line. The ACU2R
gives consolidated alarm signals to the sum alarm relays “Urgent” and “Non-urgent”.
The alarm status is also analyzed by the ACU48R via the internal monitor bus to poll each of the
possible 24 (=12 dual) LTUs within the subrack and to signal the alarm status to two alarm
relays “Urgent” and “Non-urgent” specific for each LTU.
Under normal LTU power conditions the two output stages of each LTU are controlled by its
microcontroller. In case of a power failure on an LTU, both the “Urgent” and “Non-urgent”
alarms will be activated on the ACU. (The ACU generates an auxiliary +5 V
DC
which is used to
pull-up the open collector alarm output stages of the LTUs.)
5.2.1.1 Alarm Conditions
Urgent Alarm:
At least one of the LTU – LEDs displays a red alarm
Power failure of any one of the LTUs
Power failure of the auxiliary +5V
DC
auxiliary supply on the ACU
Power failure of both –48V
DC
supplies