SZ-DOC-W5-1.pdf LTU/NTU
Version: 1.5 Operating Manual
107 Revision: 2002-09-10
11.2 Power Supply
Power consumption depends on operation mode 1p/2p, line rate, data rate of UIF and transceiver
assembly.
11.2.1 LTU
Supply Voltage: -40.5V
DC
.. -72V
DC
Power consumption (dependent on line rate and remote powering current):
Remote
Power
OFF
Remote Power ON
Additional
Power Consumption
0mA 10mA 50mA
total local total local total local
SZ.866.V711, dual link 2p 6.6/8.5 0.8/1.2 0.8/1.2 5.8/6.1 1.2/1.7 25.6/26 4.0/4.4
SZ.866.V511, dual link 1p 3.8/5.4 1.0/1.2 1.0/1.2 3.4/3.5 1.2/1.3 13.1/13.4 2.3/2.6
SZ.866.V788, dual link 2p 6.6/9.1 0.8/1.2 0.8/1.2 5.8/6.1 1.2/1.7 25.6/26 4.0/4.4
Note: Watson 5 LTUs are supposed to be used with the subrack SZ.379.V3WDA having a 16A
fuse.
11.2.2 NTU
Power consumption (dependent on line rate):
Local Power Supply Remote Power Supply
Supply Voltage -40.5V
DC
.. -72V
DC
-112V
DC
.. -65V
DC
at NTU DSL-
Connector
SZ.886.V410, 2p 3.9 - 4.9 3.7 - 4.6
SZ.886.V480, 2p (up to 4608kbit/s) 4.0 - 6.0 3.7 - 5.7
SZ.886.V310, 1p 2.8 - 3.7 2.6 - 3.4
SZ.886.V380, 1p 2.9 - 3.6 2.8 - 3.5
SZ.886.V418, 2p (up to 4608kbit/s) 4.4 - 6.3 4.0 - 6.0
11.3 Environment
11.3.1 Climatic Conditions
Storage: ETS 300 019-1-1 Class 1.2 -25°C … +55°C
Transportation: ETS 300 019-1-2 Class 2.3 -40°C … +70°C
Operation: ETS 300 019-1-3 Class 3.2 -5°C … +45°C
11.3.2 Safety
According to EN 60950:2000 (IEC60950:1999)